Short-circuit

0112/2///62683#ACC040

short-circuit conditions, stated by the manufacturer, which the device can make, withstand or break satisfactorily

Hierarchy#

Ancestors (top) → ACC040 (highlighted) → subclasses and powertype instances. Capped at 12 each; see the full lists in the sections below.

Higher level classes2#

Declared properties25#

25 / 25
ACE700interrupting rating, a.c., 120 VREAL_MEASURE_TYPE

the highest RMS symmetrical current at a rated voltage of 120 V a.c. that a device is intended to interrupt under standard test conditions

value of the breaking capacity at a rated operational voltage of 400 V a.c., for which a specified test sequence includes the capability of the circuit-breaker to carry its rated current continuously, corresponding to one of the specified percentages of the rated ultimate short-circuit breaking capacity

value of the prospective breaking current at a rated operational voltage of 400 V a.c., for which a specified test sequence does not include the capability of the circuit-breaker to carry its rated current continuously

ACE703interrupting rating, a.c., 480 VREAL_MEASURE_TYPE

the highest RMS symmetrical current at a rated voltage of 480 V a.c. that a device is intended to interrupt under standard test conditions

ACE704interrupting rating, a.c., 600 VREAL_MEASURE_TYPE

the highest RMS symmetrical current at a rated voltage of 600 V a.c. that a device is intended to interrupt under standard test conditions

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device; type 2: under short-circuit conditions, the contactor or starter shall be suitable for further use; at the given rated operational voltage of 400 V a.c.

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device; type 1: under short-circuit conditions, the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement of parts at the given rated operational voltage of 480 Y/277 V

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device; type 1: under short-circuit conditions, the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement of parts at the given rated operational voltage of 600 Y/347 V

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device at the given rated operational voltage of 400 V

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device; type 2: under short-circuit conditions, the contactor or starter shall be suitable for further use at the given rated operational voltage of 230 V a.c.

value of the prospective short-circuit current, declared by the assembly manufacturer, that can be withstood for the total operating time (clearing time) of the short-circuit protective device under specified conditions

ACE711rated peak withstand currentREAL_MEASURE_TYPE

value of peak short-circuit current declared by the assembly manufacturer, that can be withstood under specified conditions

value of the breaking capacity for the rated operational voltage of 230 V a.c., for which a specified test sequence includes the capability of the circuit-breaker to carry its rated current continuously, corresponding to one of the specified percentages of the rated ultimate short-circuit breaking capacity

value of the prospective breaking current for the rated operational voltage of 230 V a.c., for which a specified test sequence do not include the capability of the circuit-breaker to carry its rated current continuously

value of the prospective breaking current for the rated operational voltage of 690 V a.c., for which a specified test sequence do not include the capability of the circuit-breaker to carry its rated current continuously

value of the breaking capacity for the rated operational voltage of 690 V a.c, for which a specified test sequence includes the capability of the circuit-breaker to carry its rated current continuously, corresponding to one of the specified percentages of the rated ultimate short-circuit breaking capacity

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device at the given rated operational voltage of 230 V

value of prospective current that a circuit or a switching device, protected by a short-circuit protective device, can satisfactorily withstand for the operating time of this device at the given rated operational voltage of 690 V

short-circuit making capacity assigned to an equipment for the rated operational voltage of 230 V, at rated frequency and at a specified power-factor, expressed as the maximum prospective peak current, under prescribed conditions

short-circuit making capacity assigned to an equipment for the rated operational voltage of 400 V, at rated frequency and at a specified power-factor, expressed as the maximum prospective peak current, under prescribed conditions

short-circuit making capacity assigned to an equipment for the rated operational voltage of 690 V, at rated frequency and at a specified power-factor, expressed as the maximum prospective peak current, under prescribed conditions

Subclasses#

No subclasses

This class is a leaf — no other classes inherit from it.

Metadata#

Version
2
Revision
1
Status
Standard
Publisher
IEC
Published in
IEC 62683-2-2:2025
Responsible committee
IEC/TC 121
Change request
C00184
Dates
  • Original: 2011-03-04
  • Current version: 2026-01-30
  • Current revision: 2026-01-30

Full source data#

Every key from the original .xls export, including multilingual variants, status, publisher, committee, and workbook-specific codes.

Raw properties (32 keys from source .xls) — click to expand
C002
C00184
C011
IEC
C012
IEC 62683-2-2:2025
C016
Standard
C017.de
1
C017.fr
2
C017.zh
1
C018.de
6/15/2017
C018.fr
3/14/2025
C018.zh
9/26/2017
C019.de
DKE, Jürgen Schütz
C019.fr
AFNOR
C019.zh
SAC, Li Hui
MDC_P001_5
0112/2///62683#ACC040
MDC_P002_1
2
MDC_P002_2
1
MDC_P003_0
2026-01-30
MDC_P003_1
2011-03-04
MDC_P003_2
2026-01-30
MDC_P003_3
2026-01-30
MDC_P004.de
Kurzschluss
MDC_P004.en
Short-circuit
MDC_P004.fr
Court-circuit
MDC_P004.zh
短路
MDC_P006.de
zufällige oder beabsichtigte leitende Verbindung zwischen zwei oder mehr leitenden Teilen, die dazu führt, dass die elektrischen Spannungsunterscheide zwischen diesen Teilen gegen null ge­hen
MDC_P006.en
short-circuit conditions, stated by the manufacturer, which the device can make, withstand or break satisfactorily
MDC_P006.fr
conditions de court-circuit, déclarées par le constructeur, que l'appareil peut établir, supporter ou interrompre de façon satisfaisante
MDC_P006.zh
两个或多个导电部件之间偶然或有意形成的导电通路,迫使这些导电部件之间的电位差等于或接近于零。
MDC_P010
0112/2///62683#ACC010
MDC_P011
ITEM_CLASS
MDC_P012
IEC/TC 121
MDC_P014
{0112/2///62683#ACE716,0112/2///62683#ACE702,0112/2///62683#ACE717,0112/2///62683#ACE715,0112/2///62683#ACE701,0112/2///62683#ACE718,0112/2///62683#ACE700,0112/2///62683#ACE703,0112/2///62683#ACE704,0112/2///62683#ACE712,0112/2///62683#ACE721,0112/2///62683#ACE722,0112/2///62683#ACE708,0112/2///62683#ACE723,0112/2///62683#ACE724,0112/2///62683#ACE725,0112/2///62683#ACE726,0112/2///62683#ACE713,0112/2///62683#ACE714,0112/2///62683#ACE705,0112/2///62683#ACE709,0112/2///62683#ACE706,0112/2///62683#ACE707,0112/2///62683#ACE711,0112/2///62683#ACE710}

Version history3#

  1. Current rev 01
    30 Jan 2026 · 11:38 UTC by BATCH 00000852
    View on cdd.iec.ch ↗
  2. superseded rev 02
    11 Jan 2020 · 22:57 UTC by BATCH 00000749
    ↓ Version JSON
    View on cdd.iec.ch ↗
  3. superseded rev 01
    16 Sep 2016 · 14:33 UTC by BATCH 00000703
    ↓ Version JSON
    View on cdd.iec.ch ↗

IEC CDD records every published revision of each entity — version number, status, timestamp, and the change request that introduced it. OpenCDD captures the full chain of custody from cdd.iec.ch; the entry marked Current is the one rendered on this page.